Quick Start
Interface Connectors
-48V Battery
The -48 VDC input connector on the Adit 600 is used for either direct DC powering
of the Adit 600 unit or for a Battery Backup connection when AC is used. There is
no power cable provided for this connector, however the connector is provided.
WARNING! POSSIBLE SHOCK HAZARD EXISTS, PLEASE FOLLOW INSTRUCTIONS
CAREFULLY.
To connect -48 VDC power:
1. Ensure that no power is present on the two wires to be connected.
2. Strip the two wires (approx. 5/16 in. bare wire) from the power source. 16 or
18 AWG insulated copper wire is recommended for power connections.
3. Insert the Battery Return and DC wires into the appropriate square holes.
4. Tighten screws to clamp wires.
5. Ensure that no bare wire shows after the wires are installed.
6. Plug connector in the -48 VDC connector, as seen below and secure with set
screws.
7. Apply power to connector from -48 VDC power source.
8. Verify with voltmeter that voltage is correct and polarity is correct.